12/12 Model 8317 Page 3 of 5
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1. No flow. 1. Check the main shut-off valve.
2. Insufficient water flow, shower and
eyewash.
2. Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
3. Insufficient water flow on eye/face
wash, however, shower is
sufficient.
3. a. Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
b. Probable clogging of flow control
due to inadequate line flushing.
Unscrew eye/face wash head and
remove the four screws to
disassemble the head. Clean flow
control and reassemble head. See
SP65 Installation Drawing for
details.
4. Eye/face wash stream does not
meet desired eye level.
4. a. Possible blocked flow control, see
above solution.
b. Possible non-leveled eye/face wash
assembly.
5. Insufficient water flow at the
showerhead, however, eye/face
wash is sufficient.
5. Probable clogging of flow control
inside shower head. Unscrew
shower head off of elbow and clean
rubber flow control.
6. Water does not drain properly. 6. Check your drain system for debris.
Check the main waste line of your
building to see if it does handle the
capacity required for the entire
drainage system.
7. Water leak between joints or
fittings.
7. Tighten loose connections. If leak
persists, the application of hot water
will sometimes reseat improperly
applied joint compound. After 30
minutes wait and retest, a persistent
leak will necessitate reassembly and
additional sealant.
For more information on Haws Products, please see our website: www.hawsco.com