LOCATION OF UNIT: The Model 8317 Emergency Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from
obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4” IPS with 30-90 psi (2-6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter
is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1-1/4” IPS.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts
are included. Use pipe joint sealant PST #565 (Loctite) on all connections.
STEP 1: Prepare the emergency shower foundation by using the floor flange
assembly as a template. Locate the three holes for the 3/8-16 UNC x 6"
anchor bolts (not supplied). They should extend 1" above the floor level.
STEP 2: Once the concrete foundation is ready (dry), assemble the floor flange
assembly to the anchor bolts, then securely fasten with 3/8-16 UNC Hex
Nuts and 3/8" washers (not supplied). Seal and tighten floor flange and (1-
1/4”) coupler. Make sure foot control holes are facing side to side.
STEP 3: Assemble plugged nipple (1-1/4” x 24”) to the floor flange assembly and
tighten with a pipe wrench. (Plugged end up).
STEP 4: Assemble the eyewash assembly and tee (1-1/4” x 1-1/4” x 1/2”) to the
24” nipple from Step three.
STEP 5: Attach nipple (1-1/4" x 31") and tee (1-1/4”) to assembly and tighten.
STEP 6: Attach nipple (1-1/4” x 24”) and tee (1-1/4” x 1-1/4” x 1) and tighten.
STEP 7: Attach nipple (1” x 9”) to valve assembly with a spud wrench.
STEP 8: Assemble the street elbow (1”) onto nipple (1” x 12-1/2”).
Attach nipple onto valve.
Attach the showerhead onto the street elbow (1”).
STEP 9: Assemble the sign onto the unit. Use the strap, screws, washers and nuts
provided, to mount the sign onto the upright. The sign should be
positioned for maximum visibility.
STEP 10: Insert the galvanized plug into the optional supply line tee that is not used.
Before connecting the supply water line to the emergency shower, FLUSH
THE LINE THOROUGHLY.